Light-engineered-displays DA Series GANG MOUNTED DIRECTORY Manual do Utilizador

Consulte online ou descarregue Manual do Utilizador para Sensores Light-engineered-displays DA Series GANG MOUNTED DIRECTORY. Light Engineered Displays DA Series GANG MOUNTED DIRECTORY User Manual Manual do Utilizador

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 2
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 0
1. Standby Voltage
12 or 24 vdc
2. Standby Current
0 ma
3. Alarm Current
Increases approximately 20 ma per
activated indicator
4. Indicators
Super Bright LED’s “Non-Polarized”
Red for AlarmYellow for Trouble
5. Activating Voltage
-Specify Positive or Negative
12 or 24 vdc
6. Operating Temperature
32°-100°F (0°-38°C)
7. Intended for indoor / dry location
Technical Specifications
General Description
109 Portwatch Way Wilmington, N.C. 28412 Phone: (800) 251-2512 Fax: (800) 251-9878
Internet: www.ledinc.com Email: [email protected]
Graphic Annunciators * Water Leak Detection
Fireman’s Smoke Control Panels * ARA Systems
DA
SERIES
DA-15AS (left)
& DA-5A (right)
DIRECTORY
GANG MOUNTED
The Da-Series annunciators are available in five, ten, fifteen, twenty, twenty-five and thirty zone
models. The annunciators can be configured with a red LED or a red and yellow LED per
window. The windows have pull-out tabs for easy field labeling.
The Da-Series annunciators use high-brightness LEDs and are available with an optional
audible alarm sonalert and silence switch. The audible is activated by an internal diode buss and
can be configured to sound upon alarm, trouble, or alarm and trouble inputs. The silence switch
includes a ring-back feature to insure the switch is not left in the silence position.
The DA-Series Annunicators are designed to be mounted on an ordinary switchbox. There are
five input zones per gang. One extra gang is required to accomodate the optional sonalert and
silence switch. NOTE: The alarm audible is not available on the 30 zone model. The annunciator
has a bright red aluminum faceplate that mounts directly to the switch box. Units can be flush or
surface mounted.
Optional gaskets are available for use in outdoor applications. However, the annunciators should
not be mounted where direct contact with rain is expected. Install under overhang.
Vista de página 0
1 2

Resumo do Conteúdo

Página 1

1. Standby Voltage 12 or 24 vdc2. Standby Current 0 ma3. Alarm Current Increases approximately 20 ma per activated indicator4. In

Página 2 - Wiring Diagram

NOTES: 1) The annunciator operates at 12 to 24 vdc. One common connection, (specify com+ or com - ), is required per for all LEDs, plus a sw

Comentários a estes Manuais